So, the separate switching & protection device is used for each source. As the fault levels at these locations are very high, protection device should have high breaking capacity & switching operations at these locations is very infrequent. Hence ACB is used at these locations. (Location: 11 & 12) Purpose of these breaker is to protect bus bar under it & provide isolation for whole system.
Generally, the capacity of
generator is smaller than the transformer ration due to economic reasons, hence
only circuit loads are operated when generator is providing the power. Please
note the generator is used as stand by source, hence transformer and generator are
not working in synchronism. If breaker 11 & 12 are closed simultaneously
there can be circulating current following through them or in worst case there
can be short circuit. To avoid this condition buscoupler (Tie breaker;
breaker 13) is used. By this arrangement all the critical loads are connected to
busbar under generator set and noncritical loads to busbar under transformer.
When EB supply is healthy breaker 11 & 13 is closed and supply is given to
all critical & noncritical loads. When generator is supplying the power the
breaker 12 is closed and only critical loads will get supply. Generally
interlocking system is used to ensure the same. Generally, ACB is used as bus
coupler.
No. of outgoing feeder are taken from the busbar for various loads.
Every feeder has its own switching and protection device. ACB/MCCB can be used
for outgoing feeders. Purpose of these breakers is to protect the underground
cable & give the backup protection to breaker 31. Panel consisting of
incoming breaker, busbar, bus coupler and no of outgoing breaker is called as
PCC panel (Power control center panel).
From outgoing feeder supply is given to loads through MCC panel. Every
MCC panel has its own incoming breaker for switching, protection, &
isolation purpose (breaker 31). Generally, MCCB/SDF is used at location 31.
From MCC panel supply is given to various motors. For control and protection
purpose every motor has motor feeder combination. Motor requires switching
along with overload, single phasing & short circuit protection. In most of
the cases switching of the motor are frequent, hence switching device should
have high life. Generally switching device is contractor, which will give the
highest operating life. For overload & single phasing protection of motor
Bi-metal relay (BMR) is used. SDF/MCCB is used as SCPD (Short circuit protection
device) & isolation purpose.
Relevant Standards:
IS/IEC: 60947
· Part 1 ---- General Rules for all products
· Part2 ---- Circuit breakers
· Part 3 ---- Switch disconnector Fuses
· Part 4 ---- Contactor/Relays/Starters
·
Fuses ---- IS;13703/ IEC
60269
·
MCB ---- IEC 60898
Switchgear Distinguishing
Features
Type |
Circuit Rating |
Fault Operating Capacity |
Frequency of Operation |
Life expectancy (No. of Operations) |
High |
High |
Infrequent |
Low |
|
BCCB |
Medium |
Medium |
Infrequent |
Low |
FUSE |
Medium/Low |
High |
Once |
Once |
SDFs |
Medium/Low |
High/Medium |
Frequent |
Medium |
CONTACTORs |
Low |
Low |
Very Frequent |
High |
Switchgear |
Switching |
Protection |
Contactor |
Y |
N |
Relay |
N |
Y |
Starter |
Y |
Y |
Switch/SD |
Y |
N |
HRC Fuse |
Y |
Y |
SFU/FSU/SDF |
Y |
Y |
Y |
Y |
|
MCCB |
Y |
Y |
MPCB |
Y |
Y |
Good
ReplyDelete