Introduction:

Air circuit breaker is a mechanical switching device capable of making, carrying & breaking current under normal & under specified abnormal conditions such as short circuit.

  

                                

In Air circuit breaker the contacts open and close in air gap at atmospheric pressure.

                         Circuit breaker switching capabilities:

 

Make

Carry

Break

No

Overload

Short Circuit

Types of ACB:

ACB can be operated manually or electrically. According to type of mechanism, ACB can be manually operated or Electrically operated. In manually operated ACB operator has to close the breaker manually by operating the mechanism of ACB through operating handle. Whereas in case of electrically operated ACB, breaker has charging motor and closing coil, breaker mechanism is charged through motor & breaker is closed by giving an electrical command to the closing coil.

Also with respect to the way of termination of ACB can be fixed type or Draw out type ACB. In fixed type of ACB Termination is done directly on breaker terminals whereas in case of draw out ACB, breaker is having additional housing (Cradle), termination is done on cradle terminals.

Hence with respect to the way of operation as well as Terminations ACB are of four types viz.

I.         Manually operated fixed type (MF)

II.     Manually operated draw out type(MDO)

III.   Electrically operated fixed type(EF)

IV.  Electrically operated draw out type(EDO)

Troubleshooting of L&T make C-Power ACB:

1. Breaker not Closing:

Probable Cause

Possible Solution

Undervoltage release not connected to supply.

Give rated voltage to undervoltage release

Undervoltage release, Shunt release, magneto thermal release connecting link not adjusted properly.

Adjust the connecting linkage of release correctly.

Magneto thermal release removed from ACB, but trip bar of release kept free.

Lock the trip bar at given position

Latch of the mechanism spring not in proper position or misplaced

Fix the spring correctly

Under voltage release coil burnt out or open circuited.

Replace the under-voltage release

Bimetal element of magneto thermal release bent permanently.

Replace the magneto thermal release.

After overload or short circuit fault, breaker not reset (only for manually reset   type breaker)

Reset the button by pressing off/reset button.

Sticking of tripping mechanism due to excess dust.

Clean the tripping mechanism with CRC 2-26 & grease them

 2. Breaker is not tripping wit under-voltage or Shunt release:

Probable Cause

Possible Solution

Shunt release does not get supply

Check control wiring of shunt release & ensure that shunt release gets supply

Supply of under-voltage release does not get cut off

Check control wiring

 

Link point of under-voltage & shunt release misplaced.

Ensure that pins are in position

Due to dust release becomes sticky

Remove the dust from the release and clean it with CRC 2-26

 3. Breaker is not charging with motor.

Probable cause

Possible Solution

Motor is not getting supply

Check the limit switch of motor. Replace it if it is damaged.

Loose connection in secondly isolating contact

Fix the secondary isolating contact properly

Motor is burnt out

Replace the motor

 4. Breaker is not tripping with manual trip push button

Probable Cause

Possible Solution

Trip push button connecting link is short

Adjust the push button link correctly

Latch of the mechanism jammed because of dust

Clean the latch of mechanism with CRC 2-26

 5. Breaker is not racking in the cradle freely

Probable Cause

Possible Solution

Threads of mechanical indicating assembly worn out.

Replace the mechanical indicating assembly.

Shutter assembly is not properly set in the cradle.

Fix the shutter assembly properly in the cradle.

Secondary isolating contacts not matching properly.

Match the fixed and moving secondary isolation contacts properly.

Dovel pin broken

Replace the Dovel pin

Telescopic rail becomes jammed.

Clean the telescopic rail with CRC 2-26. Remove dust, grease & re-lubricate it.

 6. Erosion of Arching Contact

Probable Cause

Possible Solution

Rough design plates of arc chutes

Clean the deion plates and side insulating strips of arc chutes with CRC 2-26

Breaker is operated without arc chute in position

Always operate ACB with arc chute in position & keep the arc chute clean.

 7. Overheating

Probable Cause

Possible Solution

Poor termination (High milli-Volts drop across termination on ACB.

Clean the terminals with CRC 2-26 and do proper re-termination. Ensure that milli volt drop within specified limits

Dusty atmosphere

Do periodic cleaning of ACB

Use of undersized cable or busbar

Use cable or busbar of adequate rating.

High ambient temperature.,

Reduce load current or select & install correct rating of ACB.

8. Breaker is not closing remotely

Probable Cause

Possible Solution

 Breaker is not in service position.                                        

 Take the breaker in service position

Closing coil not getting supply             

 Check control circuit and ensure coil gets supply.

 Closing coil burnt out or open circuited.                                

 Replace the closing coil

9. ACB is not tripping in case of overload or short circuit fault.

Probable Cause

Possible Solution

Connection between C.T. and protection release is loose or open circuited.

Tighten the terminals in case of open circuited

Overloading setting of protection release is more than actual load current

Make the overload setting as ACB as pr actual load current

Protection release linkage not adjusted properly

Connect the linkage of protection release to trip bar properly & ensure its tripping operation.

 10. Main Contacts one of the pole of ACB not closing

Probable Cause

Possible Solution

Excessive dust accumulated in the pole assembly.    

Clean the pole assembly mechanism with CRC 2-26.

Remove grease  and dust with brush & apply fresh grease.

Nylon rollers of the pole assembly are not rotating smoothly.    

Clean the nylon rollers with CRC 2-26 and re-lubricate  them.

Pole connector setting disturbed    

Consult the manufacturer of ACB 

Nylon rollers of the pole assembly are broken

Consult the manufacturer of ACB 

 11. Pitting of the main contacts.

Probable Cause

Possible Solution

Arching contact gap is not adjusted properly

Adjust the gap of arching contacts, it should be  0.9 mm approximately.

Thickness  of arcing contact is reduced below the specified limit(>0.5 mm)

Replace the fixed and moving arcing contacts.