Transformer protection
Protection Devices
The following
discusses protection devices typically delivered as a part of the power transformer delivery.
1.
Buchholz (Gas)
Relay
2.
Pressure Relay
3.
Oil Level Monitor Device
4.
Winding
Thermometer
The power transformer protection as a whole and the utilization of the below presented protection devices are not discussed here.
1. Buchholz (Gas) Relay
The Buchholz
protection is a mechanical fault detector for
electrical faults in oil-immersed
transformers. The Buchholz (gas) relay is placed in the piping between the
transformer main tank and the oil conservator. The conservator pipe must be
inclined slightly for reliable operation.
Often
there is a bypass pipe that makes it possible to take the Buchholz relay out of
service.
The Buchholz
protection is a fast
and sensitive fault detector. It works independent of the
number of transformer winding, tap changer position and instrument
transformers. If the tap changer is of the on-tank (container) type, having its
own oil enclosure with oil conservator, there is a dedicated Buchholz relay for
the tap changer.
A typical Buchholz protection comprises a pivoted float (F) and a pivoted vane (V) as shown in Figure 1. The float carries one mercury switch and the vane also carries another mercury switch. Normally, the casing is filled with oil and the mercury switches are open.
When minor fault occurs…
Here is
assumed that a minor fault occurs within the transformer. Gases produced by minor faults rise from the fault location to the
top of the transformer. Then the gas bubbles pass up the piping to the
conservator. The gas bubbles will be tapped in the casing of the Buchholz
protection.
This means that
the gas replaces the oil in the casing. As the oil level falls, the float (F)
will follow and the mercury switch tilts and closes an alarm circuit.
When major fault occurs…
It is
also assumed that a major fault, either to earth of between phases or winding,
occurs within the transformer. Such
faults rapidly produce large volumes of gas (more than 50 cm3/(kWs) and oil
vapor which cannot escape.
They therefore
produce a steep buildup of pressure and displace oil. This sets up a rapid flow
from the transformer towards the conservator. The vane (V) responds to high oil
and gas flow in the pipe to the conservator. In this case, the mercury switch
closes a trip circuit. The operating time of the trip contact depends on the location of the fault and the magnitude of the fault current.
Tests carried out with simulated operating
conditions have shown that operation in the time range 0.050-0.10 seconds is
possible. The operating time should not exceed 0.3 seconds.
The gas accumulator relay also provides a long-term accumulation of gasses associated with overheating of various parts of the transformer conductor and insulation systems. This will detect fault sources in their early stages and prevent significant damage.
Figure 2 – A typical outlook of a Buchholz relay with flanges on both sides for pipe connections
When the
transformer is first put into service, the air trapped in the winding may
give unnecessary
alarm signals. It is customary to remove the air in the power
transformers by vacuum treatment during the filling of the transformer tank
with oil.
The gas
accumulated without this treatment will, of course, be air, which can be
confirmed by seeing that it is not inflammable.
In addition, the Buchholz relay can detect if the oil level falls below that of the relay as a result of a leakage from the transformer tank.
Many power transformers with an on-tank-type tap changer have a pressure protection for the separate tap changer oil compartment. This protection detects a sudden rate-of-increase of pressure inside the tap changer oil enclosure. Figure 3 shows the principle of a pressure relay
Figure
3 – Pressure relay
When the pressure in front of
the piston exceeds the counter force of the spring, the piston will move
operating the switching contacts. The micro switch inside the switching unit is
hermetically sealed and pressurized with nitrogen gas.
An internal fault in an oil-filled transformer is
usually accompanied by over pressure in the transformer tank.
The simplest form of pressure
relief device is the widely used frangible disk. The surge of oil
caused by a heavy internal fault bursts the disk and allows the oil to discharge
rapidly. Relieving and limiting the pressure rise prevent explosive rupture of
the tank and consequent fire.
Also, if used, the separate tap changer oil enclosure can be fitted with a pressure relief device.
A drawback of the frangible
disk is that the oil remaining in the tank is left exposed to the
atmosphere after a rupture. This is avoided in a more effective device, the
pressure relief valve, which opens to allow the discharge of oil if the
pressure exceeds the pre-adjusted limit.
By providing the transformer with a pressure relief
valve, the over pressure can be limited to a magnitude harmless to the
transformer.
If the abnormal pressure is
relatively high, this spring-controlled valve can operate
within a few milliseconds and provide fast tripping when suitable contacts are
fitted. The valve closes automatically as the internal pressure falls below a
critical level.
3. Oil Level Monitor Device
The top-oil
thermometer has a liquid thermometer bulb in a pocket at the top of the transformer. The thermometer measures
the top-oil temperature of the transformer. The top-oil thermometer can have
one to four contacts, which sequentially close at successively higher
temperature.
With four contacts fitted, the two lowest
levels are commonly used to
start fans or pumps for forced cooling, the third level to
initiate an alarm and the fourth step to trip load breakers or de-energize the
transformer or both.
Figure 7 – Capillary type of top-oil temperature measurement device
The top-oil
temperature may be considerably lower than the winding temperature, especially
shortly after a sudden load increase. This means that the top-oil thermometer
is not an effective overheating protection.
However, where
the policy towards transformers’ loss of life permits, tripping on top-oil temperature may be satisfactory. This has the added advantage of directly monitoring the oil temperature
to ensure that it does not reach the flash temperature.
4. Winding Thermometer
The
winding thermometer creates an image of the hottest part of the winding. The top-oil temperature is measured with a similar method as
introduced earlier. The measurement is further expanded with a current signal
proportional to the loading current in the winding.
This current
signal is taken from a current transformer located inside the bushing of that particular winding. This current
is lead to a resistor element in the main unit. This resistor heats up, and as
a result of the current flowing through it, it will in its turn heat up the
measurement bellow, resulting in an increased indicator movement.
Figure 9 – Top-oil thermometer and winding thermometer main units fitted on the side of a power transformer
The
temperature bias is proportional to the resistance of the electric heating
(resistor) element.
The result of
the heat run provides data to adjust
the resistance and thereby the temperature bias. The bias
should correspond to the difference between the hot-spot temperature and the
top-oil temperature. The time constant of the heating of the pocket should
match the time constant of the heating of the winding.
The temperature
sensor then measures a temperature that is equal to the winding temperature if
the bias is equal to the temperature difference and the time constants are
equal.
The winding thermometer can have one to four contacts,
which sequentially close at successively higher temperature.
With four
contacts fitted, the two lowest levels are commonly used to start fans or pumps for forced cooling, the third level to
initiate an alarm and the fourth
step to trip load breakers or de-energize the
transformer or both.
In case a power
transformer is fitted with top-oil thermometer and winding thermometer, the
latter one normally takes care of the forced cooling control
Transformer maintenance schedule are classified into various categories
Hourly Basis
- Check the loading ampere of the transformer against the rated figure
- Check the voltage of the transformer against the rated figure.
- Check the oil temperature of the transformer
(A) Daily Basis:
- Check Oil Leakage from any point of transformer
- Check the oil and winding temperature
- Check the oil level of the main conservator
- Oil level in the bushing
- Check Breather Condition of the transformer( Oil Cap level and silica gel condition check)
- Check oil level in the buchholz relay
- Check oil level of the transformer
- Check the dirt on the bushing
- BVD and oil insulation testing
- Check the cooling fan auto manual function if applicable
- Check the OLTC mechanism operation
(D) Half Yearly
- Transformer oil testing
- Check the buchholz relay function completely
- Check the transformer marshaling box
- Transformer insulation resistance test
- Transformer Earthing test
- Transformer oil complete check
- Transformer body cleaning and paint work
- All power and control terminal tightness and overheating
.
ReplyDelete